AC90 600V

Technical details

Conductor #14 AWG, #12 AWG, #10 AWG two, three or four copper conductors solid copper #8 AWG through #2 AWG compact round concentric lay class “B” stranded copper
Armour Aluminum interlocked armour
Insulation Cross-linked Polyethylene (XLPE) Type RW90
Temperature -40°C to +90°C
Ground #14 AWG, #12 AWG, #10 AWG Two, three or four copper conductors solid copper #8 AWG through #2 AWG compact round concentric lay class “B” stranded copper
Approvals Industry compliances: CSA Standard C22.2 No. 51 No. 38 and No. 2256
RoHS Flame test compliances: CSA ST1 and FT4
Application For exposed and concealed wiring in dry locations only.
For use in ventilated and non-ventilated and ladder-type trays in dry locations
Colour Coding 2C – Black, White 3C – Black, White, Red (pictured) 4C – Black, Red, Blue, White

**Copper bonding wire supplied with copper conductors. Aluminum bonding wire supplied with aluminum conductors.
Colour Code: 2C – Black, White 3C – Black, White, Red 4C – Black, Red, Blue, White. #For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable ampacity for sizes #6, #2 and #4/0 AWG aluminum shall be 60, 100 and 200 amperes respectively. #2/0 AWG copper shall be 200 amperes. In these cases, the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied. Assuming 4th conductor is the neutral of a balanced 3 phase 4 wire system.